2002 N.E.C.
Swimming Pool Electrical Codes

Gunther Home Inspections

ELECTRICAL WIRING REQUIREMENTS FOR SWIMMING POOLS

2002 National Electrical Code / 2002 Residential Code of New York State

ALL INGROUND POOLS AND ANY POOL OVER 18' IN DIMENTION THAT IS ABOVE GROUND AND HOLDING WATER GREATER THAN 42" DEEP IS TO BE CONSIDERED A PERMINENTLY INSTALLED POOL

  1. Pool Pump Receptacle (Outlet) and Wiring Method
    a
    . If a pump motor is located within 5' - 10' from the outside pool wall, the receptacle must be a single twist-lock outlet and Ground Fault Circuit Interrupter (GFCI) protected.
    b. The Receptacle must have a weatherproof cover that can be closed when the cord is plugged in.
    c. The circuit line for the pump motor must be a continuous line going directly to the panel box, and is to be isolated from all other receptacles.
    d. Wire for the pump motor shall not be less than #12 AWG insulated copper grounded wire, and if buried, must be in conduit. (except when entering a building the wire can change) (Cannot use UF Cable for the pool pump receptacle if the wire is buried)
    e. Conduit
    i. PVC - All PVC conduit must be buried at least 18" deep*
    ii. Metal - All Rigid Metal Conduit must be at least 6" deep*
    * Wires used in conduit must be single strand wires (ex: THHN, XHHN, etc) NO UF CABLE
  2. Convenience Receptacle (Outlet)
    a. At least one (1) convenience receptacle must be located not closer than 10' but not further than 20' from the outside pool wall
    b.
    Convenience receptacle must be GFCI protected.
    c. Must have a weatherproof cover where exposed to the weather
    d. Must be separate from the pool pump outlet wiring.
    e. Wiring
    i. UF cable if buried must be at least 24" deep
    ii. PVC - All PVC conduit must be buried at least 18" deep*
    iii. Metal - All Rigid Metal Conduit must be at least 6" deep*
    * Wires used in conduit must be single strand wires (ex: THHN, XHHN, etc) NO UF CABLE
  3. Bonding The Pool
    a. All metal parts must be bonded together using a #8 (or larger) solid copper wire.
    b. Must use non-corrosive clamps.
    c. Recommend bonding in two (2) spots going way around the pool.

Check with your local building department for any additional requirements and/or restrictions prior to beginning work

 


 


Should you have questions, problems or
suggestions regarding our web site please contact our WebMaster

[ ABOUT GHI "HOME" ][ HOME INSPECTION ][ INSPECTION FEES ][ SET AN APPOINTMENT] [RADON TESTING ][ PEST INSPECTIONS ][ CUSTOMER TESTIMONIALS ][ FEATURE TOPICS] [ BROKERS AND REAL ESTATE AGENTS ][SCHEDULE APPOINTMENT ON-LINE][CONTACT US ]

Gunther Home Inspections, Inc.
Voice 585-349-3900 - Fax 585-349-3834
2767 Dewey Avenue - Rochester, NY 14616
www.InspectNY.com

© 1998-2011 Gunther Home Inspections, Incorporated